SANS 827:2011 (Natural Gas) & SANS 10087-1 (LPG) referenced — Darcy-Weisbach / Colebrook-White pressure drop calculation.
Engineering estimate — not a compliance certificate.
Pipe schedules, fitting equivalent-length values, and pressure-drop allowances used here are typical
reference figures. Confirm current clause numbers and tables in SANS 827:2011, SANS 10087-1 and
SANS 1067-2, and have the final design checked/signed off by a registered gas practitioner (LPGSA/SAQCC Gas)
before installation.
Regulatory Reference
Maximum pressure drop: 300 Pa (0.3 kPa) — SANS 827:2011 / SANS 10087-1.
Minimum LPG pipe size: DN20 (steel-equivalent).
Copper pipe standard: SANS 1067-2.
HDPE burial depth: 500 mm minimum, buried installation only.
Pipe cleaning/preparation: internal bore must be clean, dry, and free of swarf/debris before jointing and pressure testing — as required by SANS 827 / SANS 10087-1.
Calculation method: Darcy-Weisbach equation with Colebrook-White friction factor (iterative), the accepted industry method for gas pipe sizing.